TECHNICAL PARAMETERS
Function: Delay OFF
Supply Terminals:A1-A2
Voltage Range: AC/DC12V-240V,50-60Hz
Burden: AC0.09-3VA/DC0.05-1.7W
Power Input:AC max.6VA/1.3W
Supply voltage tolerance: -15%; +10%
Supply Indication: Green Led
Time Range: 0.1s-10days,ON,OFF
Time setting: Potentionmeter
Time deviation: 10%-Mechanical setting
Repeat accuracy:
Temperature coefficient: 0.05%/°C,at=20°C(0.05%°F=at 68°F)
Output: 1 x SPDT; Current Rating: 1x16A (AC1)
Switching voltage: 250VAC/24VDC
Min. breaking capacity DC: 500mW
Mechanical Life: 1x10,000,000 cycles
Electrical Life(AC1): 100,000 cycles
Reset time: max.200ms
Operating Temperature: -20°C ~ 55°C / -4°F ~ 131°F
Storage Temperature: -35°C ~ 75°C / -22°F ~ 167°F
Protection Degree: IP20
Overvoltage cathegory: III
Pollution degree:2
Installation: DIN rail mounting or Screw mounting
Max.cable (size): Solid wire max.1x2.5 or 2x1.5/with sleeve max. 1x2.5(AWG12)
FUNCTION FEATURESTime range 0.1s~10 days divided into 10 ranges for your choice.
Comfortable and single function time-range can setting by front panel.
Single-function relay with possiblity of time setting by a potentiometer.
Relay status is indicated by LED:Green for Power indicator,Red for Output indicator.
1-MODULE,DIN rail mounting. Ultra-small size,only 18mm width,mounted with 35mm DIN Rail .
WIDELY APPLICATION The time relay can be used for Pump delay time after switching heating off,switching of fans