Spec:
Item Type: Dual Power Automatic Transfer Switch
Material: PC and silver
Model: NLQ3 125 4P
Rated Current le: 100A
Insulation Voltage Ui: AC690V
Rated Voltage Ue: AC110V
Frequency: 50 or 60Hz
Rated Control Voltage US: 110VAC 85% Us to 110% Us
Level: PC level
Specification: 4P
Service Life:
Electrical: 2000 times
Mechanical: 5000 times
Rated Short Circuit Current: 50kA
: RT16 00 63A
Rated Impulse Withstand Voltage: 8kV
Auxiliary Circuit: 2 relays, each with two sets of contact capacity: AC110V50HZ le=5y
Touch time: Operation Conversion Time:Return Time: Closing Time:
How to Use:
1. Please check the integrity of the ATS before installation, open or close the ATS with the operating handle, check the flexibility of the drive and test the generation and disconnection conditions of each stage of the load for normal and standby power.
2. Use the wiring according to the selling point diagram.
PackageList:
1 x Dual Power Automatic Transfer Switch
Note:
1. The maximum ambient temperature should not exceed 40°C, the minimum should not be lower than ‑5°C, and the average temperature within 24 hours should not be higher than 35 °C.
2. The altitude of the installation site should not be higher than 2000m.
3. When the maximum temperature reaches 40°C, the relative humidity of the installation site should not exceed 50%; when the temperature is the lowest temperature ‑5°C, the relative humidity is high, for example: the temperature is 25 °C, and the relative humidity is 90%. Due to temperature changes, special measures should be taken to deal with occasional condensation on the surface of the product.