Note:
1. After installation, you must check if frequency is correct. When unloaded, set the "mechanical speed controller" to 62Hz, "electronic governors" set to 60Hz
2. After confirming that the Hertz is correct, the AC output should also be measured, the voltage should be 124VAC at 62Hz or 120VAC at 60Hz without load, if the voltage is too high or too low, adjust the brass screws on the potentiometer accordingly until the voltage is correct
3. Correct Wiring: Ensure that input and output ports are connected correctly, incorrect connections may cause voltage regulator to malfunction or even damage equipment
4. Input Voltage Range: Ensure that input voltage is within the working range of voltage regulator, excessive or insufficient input voltage may cause the voltage regulator to fail or be damaged
5. Heat Dissipation Treatment: The voltage regulator generates heat during operation, ensuring good heat dissipation measures to prevent overheating
6. Load Limit: Do not exceed the rated load of the voltage regulator, excessive load may cause voltage regulator to overload, thereby affecting its stability and lifespan
7. Regular Inspection: Regularly check the working status and wiring of the voltage regulator to ensure its normal operation